Troubleshooting guide
2-4. Output configuration
Option 1:
Option 2:
Option 3:
To Load 2
To Load 1
L 1
N1
L 2
N2
L
N
There are 2 sets of low-voltage outputs (104/110/115/120V) on L1-N1 & L2-N2. Each set is able to provide 50% of the UPS
rated current. Connect one load to L1-N1 and the other load to L2-N2.
After connecting L1&L2 and N1&N2, it becomes one low-voltage output (104/110/115/120V) at L1-N1 for 100% of the UPS
rated current. Connect load to L1-N1 or L2-N2.
After connecting N1 and L2, it becomes one high-voltage output (208/220/230/240V) at L1-N2 for 100% of the UPS rated
current. Connect load to L1-N2.
To Load
L 1
N1
L 2
N2
L
N
To Load
L 1
N1
L 2
N2
L
N