Troubleshooting guide

6. Technical specifications
Voltage
range
Overload
Transfer time
AC mode
Battery mode
Dimensions (mm)
Net weight (kg)
Operation temperature
Operation humidity
Operation altitude**
Audible noise
Smart RS-232 or USB
Optional SNMP
0 ~ 40°C (the battery life will down when > 25°C)
<95 % and non-condensing
<1000m
Supports Windows® 2000/2003/XP/Vista/2008,
Windows® 7, Linux and MAC
Power management from SNMP
manager and web browser
AC mode
Battery mode
Line
Inverter
Inverter
Type & quantity
Recharge time
Charging current
Charging voltage
Less than 58dB @ 1 meter Less than 60dB @ 1 meter
592 x 250 x 826
124
592 x 250 x 826
142
Battery
Bypass
ECO
Frequency range
Phase
Power factor
Single phase with ground
0.99 at 100% Load
100%~105%: 10min
105%~115%: 1min
>115% : 1sec
100%~105%: 30sec
105%~115%: 10sec
>115% : 1sec
Output voltage
AC voltage regulation
Frequency range (synchronized range)
Frequency range (batt. mode)
Current crest ratio
3:1 max
0 ms
0 ms
<10 ms
> 84%
> 83%
1.0 A ± 10% (max.)
14.4 V ± 1%
Harmonic distortion 3 % @ 100% linear load; 10 % @ 100% non-linear load
12 V / 7 Ah x 20
7 hours to 90% capacity
12 V / 9 Ah x 20
9 hours to 90% capacity
104/110/115/120VAC or 208/220/230/240VAC
± 3%
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Low line transfer
Low line comeback
High line transfer
High line comeback
6000 VA / 4800 W 10000 VA / 8000 W
Low line transfer voltage + 10V
300 VAC ± 3 %
High line transfer voltage - 10V
110 VAC ± 3 % at 50% Load
176 VAC ± 3 % at 100% Load
Model
CAPACITY*
INPUT
OUTPUT
EFFICIENCY
BATTERY
PHYSICAL
ENVIRONMENT
MANAGEMENT
FDC-006K FDC-010K