Troubleshooting guide
08: Bypass mode setting
09: Battery backup time setting
Interface Setting
Parameter 2:
OPN: Bypass allowed. When selected, the UPS will operate
in Bypass mode depending on the enable/disable
bypass setting.
FBD: Bypass not allowed. When selected, the UPS
will not be able to operate in Bypass mode under
any circumstances.
Parameter 3:
ENA: Bypass enabled. When selected, it means that
the Bypass mode is activated.
DIS: Bypass disabled. When selected, the automatic
bypass may be used, but manual bypass is never allowed.
Manual bypass make possible for users to manually operate
the UPS in Bypass mode. For example, by pressing the
OFF button in AC mode, it will cause the unit to start running
in Bypass mode.
Interface Setting
Parameter 3:
000~999: Sets the maximum backup time from
0min to 999min. UPS will shut down to protect the battery
after backup time expires. The default value is 990min.
DIS: When you disable the battery discharge protection,
the backup time will depend on battery capacity.