Troubleshooting guide

04: Frequency range for bypass
05: ECO mode enable/disable
06: Voltage range for ECO mode
07: Frequency range for ECO mode
Interface Setting
Parameter 2: Sets the acceptable low frequency
for bypass operation.
50 Hz system: Setting ranges from 46.0Hz to 49.0Hz.
60 Hz system: Setting ranges from 56.0Hz to 59.0Hz.
The default value is 46.0Hz/56.0Hz.
Parameter 3: Sets the acceptable high frequency
for bypass operation.
50 Hz: Setting ranges from 51.0Hz to 54.0 Hz.
60 Hz: Setting ranges from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.
Interface Setting
Parameter 3: Enables or disables the ECO feature.
You may choose between the following two options:
DIS: disables the ECO feature
ENA: enables the ECO feature
When the ECO feature is disabled, the voltage and
frequency range can still be set for this mode, however,
such parameters will take effect only if the ECO function
has been enabled.
Interface Setting
Parameter 2: Sets the low voltage point in ECO mode.
This setting ranges from 5% to 10% of the nominal voltage.
Parameter 3: Sets the high voltage point in ECO mode.
This setting ranges from 5% to 10% of the nominal voltage.
Interface Setting
Parameter 2: Sets low frequency point for ECO mode.
50 Hz system: Ranges from 46.0Hz to 48.0Hz.
60 Hz system: Ranges from 56.0Hz to 58.0Hz.
The default value is 48.0Hz/58.0Hz.
Parameter 3: Sets the high frequency point for ECO mode.
50 Hz: Ranges from 52.0Hz to 54.0 Hz.
60 Hz: Ranges from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.