eVault Specific Instructions
The Guardian connects to the last remaining communication port on the battery-battery communication
circuit. It does NOT connect to the eVault canbus port.
Move the canbus resistor toggle switch to the OFF position (the canbus resistor is included inside the
Guardian unit). If more than one eVault MAX are installed, only the primary battery unit should have the
canbus resistor in the ON position.
For outdoor installations, you may need to install a female-female ethernet connector to transition to
the weatherproof communication cabling, in order to maintain the weatherproof rating of the eFlex
battery. This custom cabling is not required for indoor eFlex installations or installations inside the
DuraRack or FlexTower.