Sol-Ark Integration Guide
 Rev 2.0 08-28-21 
Fortress Power - Sol-Ark Inverter Guide 
505 Keystone Rd, Southampton, PA 18966 . (877) 497 6937. sales@fortresspower.com . Fortresspower.com  
7 
Steps 10 - Verification: 
Confirm all batteries are “working” before leaving site by confirming amperage is flowing in or out of 
each battery. If the battery is showing 0 amps while other batteries are working, then that battery has 
not been commissioned correctly. 
eFlex + Instructions 
On eFlex batteries, apply a charge current and 
confirm the state-of-charge light is blinking on 
each battery or 
confirm using 
the Fortress 
firmware 
update tool.  
eVault MAX / Classic Instructions 
Touch the LCD screen to see that amperage is 
flowing in or out of each eVault. If either eVault 
is not turning on, switch the master-slave roles 
on the eVaults in the communication circuit and 
power cycle the batteries. 
Step 10 – Calibrating the State of Charge Controller (optional):  
Note: This step can be performed after installation remotely by changing settings within Powerview if 
necessary. It can be performed during commissioning if time allows but is not usually necessary to do so. 
Calibrating the SoC controller should occur 
automatically, but can be forced manually 
by charging to 56V. Disable BMS control 
and putting the inverter in “voltage based 
control”.  
The inverter should already programmed to 
float/absorb at 56V. Let the batteries 
operate like this on a sunny day to bring 
the batteries gently to 56V via float charge. 
This will recalibrate the SoC controller. 
Then return the battery settings to BMS 
04 % charged control. 
eFlex-specific instructions: Useful if an eFlex is not showing four “state of charge lights” when charged 
full or if only reaching a 99% during normal operation.  
eVault-specific instructions:  Useful if eVault shows 100% when voltage is less than 54V.  
A blinking State of Charge 
Indicator Light confirms that the 
eFlex is charging. 
✓ 
✓ 
✓ 