Step 8 – Confirm BMS communication. 
After completing steps 1-7, go to the home screen of the SolArk unit, touch the gear icon, and select the 
new “Lithium Batt Info” option in the setup menu options screen. If data appears across the top of the 
menu option as well as across line 2 only, then the battery is communicating to the SolArk. Otherwise 
this option will only populate with zeroes. 
Step 9 – Program Grid Parameters. 
Go back to the home screen, touch the gear icon, and select “Grid Setup”. The Grid Parameters menu 
will appear and the Grid Limiter Function will be the first tab. You may still need to program other tabs, 
but this Grid Limiter tab plays an important role in battery behavior. The programmed levels are user 
specific, so think carefully when programming this menu relative to the specific job site and grid policy. 
Grid Sell – Select to sell back to the grid when 
the batteries are 100% full. 
Limited to Home – Select when not allowed 
to backfeed the grid or when utility solar 
buyback rates is horrible. Typically requires 
200A SolArk CTs around the main grid feed.  
Limited to Load – Select when off grid. 
Time-of-use – Almost always select this 
feature even when off-grid. It is useful not 
only for time-of-use rate structures but to 
optimize battery use conditions such as 
grid/generator charging. 
Charge Time of Use Column – The battery 
will stop being used at the % programmed. 
Checking the box will force a grid charge. 
Discharge Time of Use Column – Select to for a sell back to the grid. Useful for utility battery incentive programs or 
where time-of-use rate structures where the utility solar buyback rate is advantageous. Not commonly used, as the 
battery will sell back to the grid if the grid sell column is checked. 
Batt % Column – If more solar power is available than load, solar will always charge the battery to 100% before 
selling back to the grid, unless the Sell column is checked. Alternately, if the battery falls below this % and grid 
power is available, the battery will switch over to grid power. Useful for keeping the battery at 20% without 
triggering a full grid recharge. 
Header data appears here 56V 185A etc…. 
 1: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 
 2: Battery Data appears here when successful 
 3: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 
 4: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 
 …….. 
 16. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 
Lithium Batt Info 
Suggested Grid-Tie Parameters 
9000 
3:00AM
M 
5:00AM
M 
9:00AM 
3:00PM 
7:00PM
M 
9:00PM 
3kW 
3kW 
9kW 
3kW 
6kW 
3kW 
30% 
20% 
100% 
100% 
60% 
45% 
✓ 