Sol-Ark Integration Guide
 Rev 2.0 08-28-21 
Fortress Power - Sol-Ark Inverter Guide 
505 Keystone Rd, Southampton, PA 18966 . (877) 497 6937. sales@fortresspower.com . Fortresspower.com  
4 
Step 6 – Plug the modified end of the cable into the correct Sol-Ark port.  
Fortress batteries communicate with Sol-Ark over RS485 modbus. Even so, Sol-Ark labels its 
communication port on its most recent communication card as the “Battery/Canbus” port. Legacy 
SolArk inverters may use the RS485 port for battery communication. 
Typical SolArk - Battery / CANbus port  Indoor 8kW unit - RJ45/485 port   Indoor 12kW Unit / RS485 Port 
Indoor 12kW - RS485/MOD port 
Step 7 – Program the first three tabs in the Battery Setup menu. 
Touch the gear icon on the main SolArk home screen to find the Battery Setup menu. Program the 
batt/charge/discharge tab as shown below. Call or email for LFP-5/10/15 settings. 
Use Batt V charged – only use this feature 
when not using BMS control. Select to 
enable voltage-based programming. 
Use Batt % Charged – Most Sol-Ark 
installations will use this feature. 
Activate Battery – does not activate the battery but instead helps the battery after deep discharges. 
Max A Charge / Discharge - Fortress requires 1 eVault or 2 eFlex per SolArk inverter in BMS control to max out the 
SolArk 185A setting. When not using BMS control or when using an undersized battery bank, limit this charge to 
55A per eFlex or 100A per eVault. Call Fortress for settings when installing LFP5/10/15 legacy batteries. 
Tempco – if this item is not programmable, the BMS is already in control. Don’t worry about it. 
RJ45 485 
RS485 
0mV/C/Cell 
0 mV/C/Cell 
Note: to recalibrate the Battery % Charged, 
uncheck the BMS Lithium Battery 04, and 
check the Use Batt V charged box. Let the 
battery run for a day of sunny weather to 
charge the battery to 56V and then renable 
BMS control. 
185A 
185A 
Battery 
CANbus 