Victron Integration Guide
Rev 2.1 09-14-21
5
Fortress Power - Victron Inverter Guide
Skip to Step 6 if you are using eVault classic
Step 4 – Battery-to-Inverter communication setup
The Fortress batteries communicate with Victron GX using three wire CAN bus.
Closed loop communication between the Fortress eFlex and eVault MAX Batteries and Victron Inverter uses the
VE.CAN bus. This is provided only on Victron GX communication modules. A unique communication cable and
communication protocal is used to connect eFlex or eVault MAX batteries with Victron VE.Can. The setup is
shown below for each battery
NOTE: eVault batteries are supported with Victron Inverters in voltage mode only.
Standard ethernet cables can be used to make the custom cable. This conversion can be made in the field with
locally procurable items, but registered Fortress installer-dealers can also purchase pre-made cables at
https://fortresspower.com/shop.
eFlex:
Modified Battery-to-Inverter Communication cable
eFlex RJ45 pins 4+5 correspond to Victron pins 7+8
Cut a standard ethernet cable
cut out wires 1+2+3 and 6+7+8, these are not used
cross wires connecting 4+5 on the eFlex to 7+8 in the Victron
VE.Can port
VE.Can