Sol-Ark Integration Guide

Notes:
a) If total charge/discharge current capacity of the batteries exceeds the inverter's capabilities, use the maximum current
settings for the inverter. For example, if you have four eFlexes and one Sol-Ark 12K inverter, based on the size of the
battery bank, 'Max A Charge' and 'Max A discharge' should be 240A each. But, Sol-Ark 12K can only carry 185A DC
going to or coming from the battery. So, in this case, both 'Max A Charge' and 'Max A Discharge' would be set to 185A.
b) If recovering a deeply discharged battery, adjust the above charge amps to 10A.
3. Next, program the 'Charge' tab in the 'Battery Setup' menu:
Notes:
a) The settings shown in the latter screenshot are the most conventional ones, hence, adjustments may be required (please
see the table below).
b) The approach described in the note "2a" applies while programing this tab as well. Additionally, current set-point ('A')
must not exceed the generators capability.
b) Larger generators are commonly tied into the grid side of the inverter rather than the dedicated generator input. Make
check-marks and current adjustments accordingly. This fact was kept in mind while creating the last two rows of the table
above.
d) It is acceptable to raise the grid or generator start triggers to increase the reserve capacity of the system.
4. Program the Discharge tab: