Sol-Ark Integration Guide
increased.
c) The battery empty voltage should not be lower than 48V. The last statement from the previous note applies to the 'Batt
Empty V'. Usually this set-point does not exceed 50V.
Running on 1 eFlex
Running 1 Sol-Ark inverter on 1 eFlex is not compliant with Fortress minimum sizing standards.
If operating with one eFlex, please adjust the following settings:
In the Batt Setup Menu, adjust amperage in the first two tabs - the batt tab and the charge tab.
If waiting on a repair -> change charge/discharge amps to 100A.
All other cases -> change charge/discharge to 60A.
Reminder: Charge deeply discharged eFlex at 10A when recovering below 49V.
EFLX - Setting Up Closed Loop
Can communication from the eFlex to Solark is only available by written permission only.
Please use the modbus settings as normal. This section is just for information purposes.
NOTICE
The following instructions are not usable on the general release firmware of the eFlex firmware, they are considered pre-
release and should not be used outside of engineering supervision.
Step 1 - Fabricate the Communication Cable
SolArk 8k
SolArk 12k
SolArk 12k Outdoor
SolArk Side
1. Pins 4/5 (CAN_H/CAN_L) are used by
the SolArk for battery CAN
communication
2. Pin 6 (logic ground) should also be
connected
3. This bus runs at 500kbps internally.