Sol-Ark Integration Guide

Performing a calibration charge quickly:
1. Complete steps 1-3 in the previous step.
2. Go into the Grid Setup menu and enable time-of-use settings.
3. Find the current time zone and set the voltage to 55.5V. Then check the "grid charge" box in the adjacent column.
3. Once the battery reaches 55.5V, the battery should displays 100% and the original settings can be restored.
Onsite:
Online: