Sol-Ark Integration Guide
Note: the eVault MAX can parallel up to 20 battery units in closed loop communication.
Battery Touchscreen
The eVault has a touch screen. The bottom corners of the eVault are touch interactive.
Battery ID, bottom left Protocol ID, bottom right
Note: Power cycle the first battery in the battery-battery communication circuit after adjusting any of these settings
on any battery in the circuit.
Battery ID
Number each battery 1,2,3,4,5.... until the end of the battery circuit.
Except, if only installing one eVault MAX, number the battery "0".
Protocol ID
1 = Sol-Ark / Any inverter
2 = SMA
3 = Reserved
4 - Victron
5 = Schneider
Battery-Inverter Communication
eVault MAX Making the Inverter Communication Cable
The eVault MAX RJ45 pins 3+5+6 correspond to SolArk pins 6+7+8 (exactly like the original eVault). eVault MAX units
are now shipping with a pre-made Sol-Ark inverter communication cables, which should begin appearing around March
2022, so check inside the box to see if a grey communication cable has been included.