Schneider Electric Integration Guide

Table Of Contents
From eVault MAX 18.5kWh to Gateway/Insight Facility
green, (wire 6) Gateway/Insight Facility port 16
green-white, (wire 3) Gateway/Insight Facility port 18
blue-white, (wire 5) Gateway/Insight Facility port 20
Battery-Battery Connection
It does not matter which battery communication ports are used for battery-battery or
battery-inverter communication. The eVault communication ports are bi-directional and
accomplish the same functions, regardless of labeling. In other words, you can connect
the battery-battery communicaiton cables in any communication ports between
batteries, and plug the inverter into either side of the battery-battery communication
chain.
One eVault battery:
It is not necessary to use the canbus terminator. Either port can connect to the inverter
communication circuit.
One or two eVault batteries:
Place the included canbus terminator on both ends of the communication circuit.
Remove one of the canbus terminators to wire any battery-inverter communication
circuit.
Three or more batteries:
Place the included canbus terminator on both ends of the communication circuit and do
not wire the battery-inverter communication circuit. Operate the battery in "voltage
mode" using "open loop" settings.