Schneider Electric Integration Guide

Table Of Contents
Universal Parameters Settings (Open Loop)
All Open Loop Settings are programmable with a SCP, Insight Local or/and Insight Cloud.
Disregard the communication cable that would go from battery to inverter.
Settings for Fortress Batteries with Schneider Inverters
Charger Setting > Custom Setting
80% DoD, 6000 cycles
Battery Type
Custom
Charge Cycle
2StgNoFloat
Bulk Voltage
54.4 V
Max Bulk Current
eFlex:55A per battery
eVault:100A per battery
eVault MAX 150 per battery
LFP-10: 70A per battery
Max Discharge Current
eFlex: 60A per battery
eVault: 160A per battery eVault MAX:
LFP-10: 100A per battery
Battery Capacity
eFlex: 105AH per battery
eVault: 360AH per battery
eVault MAX: 360AH per battery
LFP-10: 200AH per battery
Max Charge Rate Percentage (%
)
eFlex:55A per battery
eVault:100A per battery
eVault MAX 150 per battery
LFP-10: 70A per battery
Divided by Total Inverter DC Amperage
Default Battery Temperature
Warm
Recharge Volts
51.3
Grid Support Volts**
53
Absorb Volts
54.4
Absorb Time
1 Hour