OutBack Integration Guide

High Battery Cut-in
Voltage
55.2V
SellRE (Offset)
Voltage Max
51.6V for “zero-outflow”, 53.6V for selling at “100% full”
Temp Sensors
Do not use temperature sensors / reduce any temperature
coefficients to as close to zero as allowed
*divide voltage by 2 for 24V FXR settings
Skybox Settings
The settings below should be programmed into the unit under the Custom choice.
Inverter
Maximum SOC
100%
Minimum SOC
20%
Absorb Charge
Timed
Absorb Voltage
55.2 Vdc
Absorb Time
02:00 hr
Float Charge
Disabled
Float Voltage
Can be left at default
Float Time
Can be left at default
Re-float Voltage
54.4 Vdc
Re-bulk Voltage
52.5 Vdc
Equalize Voltage
54.4 Vdc
Minimum Equalize Time
00:00
Max Charge Current (Adc)
LFP-5 & LFP-10: 50Adc
eVault: 100Adc
eFlex: 60Adc
Max Discharge Current (Adc)
LFP-5 & LFP-10: 90Adc
eVault: 125Adc
eFlex: 60Adc
Grid Charge Limit (kW)
Site specific
Low Battery Cutout
50 Vdc
LBCO Delay
130 seconds
Low Battery Restart
51.2 Vdc
High Battery Cutout
56.0 Vdc