OutBack Integration Guide

Unpack batteries and check voltage
1. Unpack the batteries and turn each battery on by itself.
2. Note the voltage of each battery and serial number. The serial numbers are
useful during warranty submittal.
3. The batteries must be within +/-0.5V of each other before commissioning.
Groups of 4 batteries or more may require a narrower voltage range to commission
properly.
4. Turn off the batteries and install them in parallel.
Notes
If the battery voltages are significantly different, one technique is to finish battery
installation and only turn on the lowest voltage battery using the pushbutton.
Charge the battery, and when the charging voltage is ~0.2V above the resting