Evault Max Install Manual

9
V4.2 11-02-21
4.1 ENVIRONMENTAL REQUIREMENTS
Application scenarios
Residential/Small Commercial
Operating Environment
Indoor and away from strong electromagnetic
radiation
Operating Temperature
14°F ~ 120°F (-10°C ~ 49°C)
IP grade
IP55
Storage Temperature
Short Duration (≤1month): -20~45°C (-4~110°F)
Long Duration (≥1month): 5~35°C (41~95°F)
Operating Humidity
0 ~ 85% non-condensing
Max charge/discharge current vs. Altitude
180A@≤2,000m
162A@2,000m~4,000m
Case Ground requirement
Use at least 6AWG (16mm²) copper wire
4.2 TOOLS & MATERIALS
The following tools and materials are required:
Positive and negative battery cables, we recommend copper cable starting at 2/0 AWG for runs of less than
10ft. Please refer to your adopted version of the National Electric Code or Local Authority Having Jurisdiction
for more guidance (not included)
Positive & Negative Terminal Lugs: 3/8in (10mm) (not included)
Electrical Conduit: 1in or 2in (not included)
Screwdriver (not included)
Battery parallel communications cable (included)
Inverter to Battery CAT5/5e communications cable (not included)
Wall Mount Stabilizers (included)
OHSA approved personal protective equipment such as the following (not included)
Insulated gloves Safety Glasses Safety Shoes