eVault Max 18.5kWh Lithium Ferro Phosphate (LFP) Installation
8.2 LCD DISPLAY WARNINGS
8.3 FUNDAMENTAL TROUBLESHOOTING GUIDE
ERROR MEANING
over high voltage protection
over low voltage protection
Discharge over-temp protection, charge over-temp protection, environmental over-temp
protection
Discharge low-temp protection, charging low-temp protection, environmental low-temp
protection
Discharge over current protection, charge over current protection
Short circuit protection
RUNNING
STATE
STATUS RUN ALM DISPLAY SOLUTION
normal
·
- - -
Battery COM
error
- Flash -
Check the communication cable and battery
ID (Cannot repeat with others) on LCD, then
restart.
Battery Wait for
parallel
Flash - -
No action necessary. This battery will join in
parallel within 1 cycle.
Charge
Total overvoltage
alarm
·
- stop charge
Charge
Total overvoltage
protection
-
·
stop charge, start discharge
Charge
Cell over-voltage
alarm
·
- stop charge
Charge
Cell over-voltage
protection
·
- stop charge