eVault Max 18.5kWh Lithium Ferro Phosphate (LFP) Installation

2. Conrm the Battery DC circuit breaker is in the “OFF” position.
3. Wire each battery’s power bus to inverter. Wire inverter’s cable to PV, Grid and Load.
4. Use the CAT5/6 cables to connect the batteries’ COM Parallel port, as illustrated in the chart below. Ensure
communication matching resistor of two terminal is set as 120Ω, while the others are set to OFF.
5. Press the button on the front of each battery for 3+ seconds one by one, until all batteries start up.
6. Touch the batteries’ LCD to set “Battery ID” from 1 to N (Parallel number) as in the picture below. Note: If used
for a single battery without parallel, set “Battery ID” as 0.
7. Touch the LCD to set Inverter “Protocol ID” to the following:
8. Use a CAT5/6 cable to connect the CAN or RS485 port of master battery (the Battery ID set as 1) to inverter
communication port.
PROTOCOL ID SUPPORT INVERTER PROTOCOL
1 Schneider MODBUS
2 Sol-Ark MODBUS
3 Victron CANBUS
4 Fortress MODBUS
5 Fortress CANBUS
6 Reserved
7 Reserved
8 Reserved