Operation and Service Manual
HCD1010R/N, HMF1010R/N, HCD1410R/N, HMF1410R/N 5
Specications
Electrical
Separate circuit and equipment ground required.
Evaporator unit
Standard electrical: 115/60/1
Maximum fuse: 15A
Amperage: 5A
Condensing unit
1010
Single-Phase
(Tecumseh)
1010
3-Phase
(Tecumseh)
1410
Single-Phase
(Tecumseh)
1410
3-Phase
(Tecumseh)
1410
3-Phase
(Larkin
LZT015M6CFIM)
1410
3-Phase
(Larkin
LCH0015MCACZ)
Electrical 208-230 V,
60 Hz
208-230 V,
60 Hz
208-230 V,
60 Hz
208-230 V,
60 Hz
208-230 V,
60 Hz
208-230 V,
60 Hz
Max Circuit
HVACR breaker
size
15A 15A 30A 25A 15A 20A
Min Circuit
Ampacity
10.7A 9.9A 19.3A 14.2A 15A 15A
Evaporator plumbing
§ 3/8" OD push-in water inlet (connection inside machine) - 3/8" OD tubing required.
§ Water shut-off recommended within 10 feet (3 m).
§ Follett recommends installation of Follett water lter system (part# 00130286) in ice machine inlet water line.
Flush drain plumbing
§ 3/4" MPT ush drain connection at the rear of the machine.
§ Drain must slope 1/4" inch per foot (6 mm per 30.4 cm).
§ Drain line should not be shared with any other piece of equipment.
§ Drain line cannot be reduced to a size smaller than 1 inch.
§ Drain should be piped without a vent.
3/4" barb x 3/4" FPT
1" Stand pipe/Drain
2 ft. x 1" OD
silicone tubing
Minimum 8"
radius
3/4" MPT x 1" slip
1" PVC Drain
2 ft. x 1" OD
silicone tubing
3/4" MPT x 1" slip
3/4" barb x 3/4" FPT
1'
1/4" per foot
(6,4 mm per 0,3 m)