Spec Sheet

7
Form# 7035
Remote 1010, 1410 series ice machine
5 – Horizon Elite ice tube runs - specifier guidelines
Long tube runs for RIDE remote ice delivery equipment
1/4"
1'
maximum
2' (60.9 cm)
beverage
dispenser
wall-mounted
ice machine
support
straps
transport tube slope
(toward ice machine)
(2 cm per meter)
minimum of
6.00" (15.24 cm)
turn/corner
radius
ice transport tube –
1 3/16" OD,
2 1/8" OD with insulation
Important specifier notes
1. 75' (22.9 m) maximum ice transport tuberun.
2. Tubing routing bends must have a
6.00"(15.24 cm) radius or larger.
3. Dips and traps are not allowed. If not
supported from underneath, secure insulated
ice transport tube at least every2' (60.9 cm)
to prevent drips andtraps.
4. Relative humidity levels above 80% in areas
where the ice machine or ice transport tube is
located may produce excessive condensation
that will cause water damage.
5.
Contact factory for recommendations
on
running tubing through a decorative soffit
orchase.
4 – Horizon Elite drain - specifier guidelines
Flush drain plumbing – For regular machine drainage
Important specifier notes: Where code allows,
follow recommendation below.
3/4" barb x 3/4" FPT
1" Stand pipe/drain
2 ft x 1" OD
silicone tubing
Minimum 8"
radius
3/4" MPT x 1" slip
1. Connect the silicone tubing to the ice machine 3/4"
drainbarb
.
2. Assemble the 3/4" barb x 3/4" FPT to the 3/4" MPT x 1"
slip. Connect the other end of the silicone tubing to the
3/4" barb
.
3. Connect the 1" slip fitting to the 1" stand pipe/drain
.
Note: Minimum 8" radius on silicone drain line. Drain line
from the ice machine must have at least 1/4" per foot
pitch (6.4 mm/0.3 m).
Note: Stand pipe/drain provided by others. All other
components provided with ice machine.
Chassis drain plumbing – To assist with condensate in high humidity areas
Important specifier notes: Where code allows,
follow recommendation below.
1. Plug must be removed from John Guest fitting.
2. Route 3/8" drain tubing through knockout in back of
docking station and insert fully into John Guest fitting
connection at the rear of the machine chassis. Route
other end of 3/8" drain tubing to drain.
3. Drain must slope 1/4" inch per foot ( 6 mm per 30.4 cm).