Installation Instructions for Remote Condenser

10
REMOTE CONDENSING UNIT
Start up and test
6
• Turn dispenser power ON if applicable
• Check current draw of compressor to verify correct electrical operation
• Put a piece of ice on bin thermostat or hold a cup under the shuttle actuator on the bin/
dispenser to verify that the evaporator unit shuts OFF; condensing unit pumps down and
shuts off.
• After shut off, restart the ice machine
Verify operation
6.1
Horizon Condenser Unit Compressor Amperage
Single Phase
Ice Machine Model Number Condensing Unit Model Number Running amps (+/- 10%)
1010R
01075365
AJA7490ZXDPN (Tecumseh) 7. 4
1010R
01354059
ASFR9510ZNAMC1 (Tecumseh) 7. 4
1410R
01075373
AWA9513ZXDPN (Tecumseh) 13.7
1410R
01354042
ASFS9516ZNAMC1 (Tecumseh) 13.7
Three Phase
Model Number Condensing Unit Running amps (+/- 10%)
1010R
01113 125
AWA9490ZXTPN (Tecumseh) 6.7
1010R
01354067
ASFR9511ZFAMC1 (Tecumseh) 6.7
1410R
01113 13 3
AWA9517ZXTPN (Tecumseh) 9.9
1410R
01278373
LZT015M6CFIM (Larkin)
LCH0015MCACZ (Larkin)
10.7
NOTICE
Ice machine MUST be cleaned and sanitized prior to operation!
Consult Operation and Service Manual provided with ice machine for cleaning and sanitizing instructions.