Installation Instructions

5
ICE MANAGER self-contained
Prepare the installation site.
2
Site preparation
2.1
Provide drainage, water supply and electrical power to within 6 feet (2m) of ice
machine in accordance with local and national codes. Outdoor installation is
not recommended and will void warranty.
Electrical
•H_C1010(A/W)BS208-230/60/1-15amps •H_C1410(A/W)BS208-230/60/1-20amps
Potablewatersupply
(3/8”push-ininternalconnection,3/8”ODtubingrequired)
•10-70psi(69-483kpa)
•45to90F(7to32C)
•Follettrecommendstheuseofanin-linewaterfiltrationsystem(item#00130286)
•Thisequipmentistobeinstalledwithadequatebackflowprotectiontocomplywith
applicablefederal,state,andlocalcodes
Condenserwatersupplyforwater-cooledsystems
(1/4”FPTinlet,1/4”FPToutlet)
•10psimin.;150psimax.(69kpamin.;1034kpamax.)
•45to90F(7to32C)
•1.5gallonsperminute(5.68litersperminute)
Drain
(3/4” MPT)
•Thedrainlinefromtheicemachinemusthaveatleast1/4”perfootpitch(6,4mm/0,3m)
Installation site requirements
2.1
NEMA
6-15
H_C1010
H_C1410
1/4"
1'
6-20
NEMA
208 V –5% to 230 V +5%