Technical Specifications Fluke VR101S Voltage
Event Recorder System
Electrical
(voltage versions, plug style, and manual languages are determined by country)
Voltage Version Operating range Nominal frequencies Power consumption
120 V 70 V to 140 V 50 Hz or 60 Hz 2 W
230 V 140 V to 270 V 50 Hz or 60 Hz 3 W
Sags, Swells and Outage Measurements
Voltage Version Range Accuracy Resolution
120 V Hot-to-neutral 0 to 200 V rms ±2 V rms 1 V rms
Neutral-to-ground 3 to 200 V rms ±2 V rms 1 V rms
230 V Hot-to-neutral 0 to 400 V rms ±4 V rms 2 V rms
Neutral-to-ground 3 to 120 V rms ±2 V rms 1 V rms
Transient Measurements
Range Accuracy Resolution
Hot-to-neutral 100 to 2500 V peak ±(10% reading +10 V) 10 V
Neutral-to-ground 50 to 2500 V peak ±(10% reading +10 V) 10 V
Phase angle 20° to 180° ±
200° to 360°
Minimum pulse width: 1 µs
Frequency Measurements
Range Accuracy Resolution
45 to 65 Hz ±0.1 Hz (3 cycles min) 0.1 Hz
Time Measurements: Events < 1 second
Accuracy Resolution
Hot-to-neutral ±0.5 cycles 0.5 cycles
Neutral-to-ground ±1 cycle 1 cycle
Events 1 second (time stamp)
Accuracy Resolution
±(2 sec/day + 8 sec) 8 sec
General Specifications
Memory size 4000 events
Power
Battery type 3.5V lithium (non-replaceable)
Battery life 7 years
Mechanical
Physical size 85 mm x 68 mm x 35 mm
Weight 120g
Environmental
Operating temperature -40 to 70°C
Relative Humidity 0 to 95% (non-condensing)
Safety
CSA Certification pending, CSA-NRTL (to UL 3111) certification pending,
Complies with requirements of EN61010-1:1993
Warranty 1 year
VR101
VOLTAGE EVENT
RECORDER
Ordering Information
(Note: At least one VR101S is required for
proper operation)
VR101S Voltage Event Recorder System
VR101 Voltage Event Recorder
Computer Hardware Requirements for
EventView software
IBM PC or 100% compatible,
with Windows
®
3.1 or Windows 95/98/NT/XP
or 2000 installed and operating
At least one free RS-232 serial port
A pointing device (recommended)
2 MB hard drive space
4 MB RAM (8 MB for Windows 95/98 or higher)
Included Accessories VR101S
VR101 Voltage Event Recorder,
Optical interface cable, 9-to-25 pin adapter,
EventView Software on two 31⁄2 inch
floppies, Users Manual
Included Accessories VR101
VR101 Voltage Event Recorder,
Instruction Sheet
Fluke Corporation
P.O. Box 9090
Everett, WA USA 98206
Fluke Europe B.V.
P.O. Box 1186
5602 BD Eindhoven
The Netherlands
Fluke (UK) Ltd
52 Hurricane Way
Norwich
Norfolk
NR6 6JB
United Kingdom
Tel.: 0207 942 0700
Fax: 0207 942 0701
E-mail: industrial@uk.fluke.nl
Visit us on the world wide web at:
http://www.fluke.co.uk
For more information call:
In the U.S.A. (800) 443-5853
or Fax (425) 456-5116
In Europe/M-East/Africa
+31 (0)40 2 675 200
or Fax +31 (0)40 2 675 222
In Canada (905) 890-7600
or Fax (905) 890-6866
From other countries
+1 (425) 456-5500
or Fax +1 (425) 456-5116
Visit us on the world wide web at:
http://www.fluke.com
© Copyright 2004 Fluke Corporation.
All rights reserved.
Printed in the Netherlands 09/04
Data subject to alteration without notice.
Pub_ID: 10808-eng
Fluke. Keeping your world