Datasheet

1650 Series Multifunction
Installation Testers
The perfect installation testing solution
Specifications
Battery type: Alkaline supplied. usable with
1.2 V NiCD or NiMH rechargeable batteries
Size (HxWxD): 100 mm x 250 mm x 125 mm
Weight: 1.17 kg
Three Years Warranty
Slim probe design
Thanks to its slim probe with integral test button,
you can safely make one-handed measurements
on hard to reach points, while keeping your eyes
on the panel.
Professional reports
Up to 500 test results can be stored in the 1653
installation tester. The data stored for each
measurement consists of the test function, user
selectable test conditions and unique references.
Model 1653 has an IR port and adaptor to enable
the results to be uploaded to a computer for
preparing professional reports.
Complete kit
All 1650 models are equipped with detachable
leads that can be replaced in case of damage or
loss. A durable hard case will protect your
instrument in tough field conditions.
AC Voltage Measurement
Range Resolution Accuracy Input Impedance Overload Protection
50 Hz – 60 Hz
500 V 0.1 V 0.8% + 3 3.3 M 660 Vrms
Continuity Testing
Range (autoranging) Resolution Test Current Open Circuit Voltage Accuracy
20 0.01
200 0.1 > 200 mA > 4 V ± (1.5%+3 digits)
2000 1
Insulation Resistance Measurement
Model Test Insulation Resolution Test Current Accuracy
Voltage Resistance Range
1653 50 V 10 k to 50 M 0.01 M 1 mA @ 50 k ± (3%+ 3 digits)
1653 100 V 100 k to 20 M 0.01 M 1 mA @ 100 k ± (3%+ 3 digits)
20 M to 100 M 0.1 M ± (3%+ 3 digits)
1653, 1652 250 V 100 k to 20 M 0.01 M 1 mA @ 250 k ± (1.5%+ 3 digits)
20 M to 200 M 0.1 M
1653, 1652, 1651 500 V 100 k to 20 M 0.01 M 1 mA @ 500 k ± (1.5%+ 3 digits)
20 M to 200 M 0.1 M + 10%
200 M to 500 M 1 M
1653, 1652, 1651 1000 V 100 k to 200 M 0.1 M 1 mA @ 1 M ± (1.5%+ 3 digits)
200 M to 1000 M 1 M + 10%
Loop Impedance Measurement
Range Resolution Accuracy
20 0.01
200 0.1 ± (3% + 10 digits)
2000 1
PFC. PSC Test
Range 0 to 50 kA
Resolution and Units I
K
< 1000 A 1 A
I
K
1000 A 0.1 kA
Accuracy Determined by accuracy of loop resistance and mains voltage measurements
RCD Testing
RCD Type 1651 1652 1653
1
AC
2
G ●●
AC
3
S ●●
4
AG ●●
AS ●●
1
AC – responds to AC
2
G – General, no delay
3
S – Time delay
4
A - Responds to pulsed signal
Tripping Time Test (T)
Current Settings Multiplier Test Current Accuracy Trip Time Accuracy
10, 30, 100, 300, 500, 1000 mA x
1
/
2
± 0% - 10% ± (1% Reading + 1 digit)
10, 30, 100, 300, 500, 1000 mA x 1 ± 10% - 0% ± (1% Reading + 1 digit)
10. 30 mA x 5 ± 10% ± (1% Reading + 1 digit)
Tripping Current (Ramp) Test – Fluke 1653 and 1652 only
Current Range Step size Dwell time Trip Current
Type G Type S Measurement Accuracy
50% to 110% of 10% of I
N
300 ms/step 500 ms/step ± 5%
RCD’s rated current
Earth Resistance Test (R
E
) – Fluke 1653 only
Range Resolution Accuracy
200 0.1 ± (2%+ 5 digits)
2000 1 ± (3.5%+ 10 digits)