Application Note
The core of a refrigeration sys-
tem is the compressor, which is
designed to pump cool refriger-
ant gas from the evaporator into
the condenser. To accomplish
this task the compressor raises
the temperature and pressure of
the low superheated gas, forcing
it into the condenser. The com-
pressor should never pump liq-
uid. This will not only damage
the compressor, but can create a
potential safety hazard.
Similar to the human heart,
the refrigeration compressor
needs to be properly maintained
and requires periodic inspection
and testing. Unfortunately, the
compressor is often ignored until
it malfunctions or stops running
altogether, at which time it gets
replaced and the system is back
up and running – temporarily.
Often times the culprit is not the
compressor, but a system failure
or desig
n problem w
ith acces-
sory equipment which killed the
compressor prematurely.
This application note describ
es
how to troubleshoot a compres-
sor and the associated problems
that can cause a system to fail
prematurely. We will discuss the
proper methods of diagnosing
and repairing system problems,
rather than just their symptoms.
Measuring the compressor
suction and discharge
pressure
Both the suction and discharge
pressures at the c
ompressor are
normally measured with a stan-
dard set of refrigeration gauges
.
However, this application note
will explain how to measure
both pressures on the suction
and high side of the system with
your digital multimeter (DMM)
and a pressure/vacuum module,
with or without your standard
gauges. If the gauges are left on
the system and used in conjunc-
tion with this test, the module
will verify the accuracy of the
standard manifold gauges.
To measure the pressures on
your DMM in conjunction with
your standard manifold gauges,
take the following steps:
•
Attach the pressure/vacuum
module hose fitting to the
refrigerant service hose on
your manifold gauge set, usu-
ally the yellow hose.
•
Attach the pressure/vacuum
module to a DMM and set the
module function to cm/in Hg.
•
Install your blue and red
hoses to the suction side and
high side of the system as
during any normal service
process.
To read the suction pressure on
your DMM, open the blue handle
on the manifold gauges. This
puts the system suction pressure
into the pressure/vacuum mod
-
ule. Read the pressure on the
digital readout and compare it to
the gauge pressures
. D
on’t be
alarmed if the pressures don’t
match exactly. Modules like the
Fluke PV350 are typically much
more accurate than a standard
set of refrigeration gauges.
To read the discharge pressure
on your DMM, close the blue
valve on your gauges and open
the red handle on the manifold
gauges. This puts the system
discharge pressure into the
module.
To remove the module, simply
reverse the process you followed
when installing the unit.
Caution: Be sure to close the
high s
ide p
ort of your gauge
s
first, and remember to remove
the refrigerant from the high
s
ide gauge by allowing the com
-
pr
e
ssor to run and pull exce
ss
refrigerant into the low side of
the system.
Troubleshooting the
HVAC/R refrigeration
cycle for mechanical
problems
Application Note
From the Fluke Digital Library @ www.fluke.com/library




