Datasheet
3 Fluke Corporation Fluke 500 Series Battery Analyzers
Specifications
Range Resolution Accuracy BT510 BT520 BT520ANG BT521 BT521ANG
Battery resistance/Strap resistance 3 mΩ 0.001 mΩ 1 % + 8
• • •
1 % + 68
• •
30 mΩ 0.01 mΩ 0.8 % + 6
• • •
0.8 %+12
• •
300 mΩ 0.1 mΩ 0.8 % + 6
• • • • •
3000 mΩ 1 mΩ 0.8 % + 6
• • • • •
Vdc 6 V 0.001 V 0.09 % + 5
• • • • •
60 V 0.01 V 0.09 % + 5
• • • • •
600 V 0.1 V 0.09 % + 5
• • • • •
1000 V 1 V 0.09 % + 5
• •
Vac (45 Hz to 500 Hz with 800 Hz
filter)
600 V 0.1 V 2 % + 10
• • • • •
Frequency (displayed with Vac and
Aac)
500 Hz 0.1 Hz 0.5 % + 8
• • • • •
AC voltage ripple (20 KHz Max) 600 mV 0.1 mV 3 % + 20
• • • • •
6000 mV 1 mV 3 % + 10
• • • • •
Adc/Aac (with accessory Fluke i410) 400 A 1 A 3.5 % + 2
• •
Temperature 0 °C to 60 °C 1 °C 2 °C (4 °F)
• •
Meter mode 999 records for each measurement position with time stamp
Sequence mode Up to 100 profiles and 100 profile templates (Each profile stores up to 450 batteries) with time stamp
The measurement is based on ac injection method. The injected source signal is <100 mA, 1 kHz.
Trigger level VAC: 10 mV, Aac: 10 A
Measurement modes
BT510 BT520 BT520ANG BT521 BT521ANG
Resistance (m)
• • • • •
Battery voltage
• • • • •
Voltage dc
• • • • •
Voltage ac and frequency (Hz)
• • • • •
Ripple volt
• • • • •
Temperature of negative battery post
(Using BTL21 straight probes)
• •
DC and ac current (and frequency)
• •
DMM mode
• • • • •
Sequence mode
• • • • •
Discharge measurement mode
• • • • •
Automatic measurement save
• • • • •
Wireless communication
• •
Memory view
• • • • •