Brochure

For more product information and detailed specifications, go to www.fluke.com
Ordering information
Fluke-PV350 Pressure
Vacuum Module
Pressure
HVAC Pressure Module
Fluke PV350 Pressure
Vacuum Module
Key features:
Compatible with all Fluke and most
popular DMMs
Digital pressure and vacuum measurements
in a single module
Transducer sealed in 316 stainless steel
compatible with a variety of liquids and
gases
Measures vacuum to 76 cm Hg
Displays results in English (psig or Hg) or
metric (kPa or cm Hg) units
Measures pressure to 3447 kPa (500 psig)
Refrigeration cycle
Quick Tips
Measuring superheat
and subcooling
To measure superheat:
1) Measure suction pressure
with a pressure module
and your digital multimeter
(DMM). Convert pressure
to temperature using your
PT chart.
2) Measure the pipe temperature
at the outlet of the evaporator
with a pipe clamp and your
temperature meter.
3) Subtract the difference
in temperatures to obtain
superheat.
To measure subcooling:
1) Measure liquid line pressure
(or discharge pressure if there
is no liquid line access valve)
with a pressure module and
your DMM. Convert the pres-
sure to temperature using your
PT chart.
2) Measure the pipe temperature
at the outlet of the condenser
with a pipe clamp and your
temperature meter.
3) Subtract the difference
in temperatures to obtain
subcooling.
Bubble Point -
Used to determine
subcooling
Constant
temperature lines
BTU’s/Lb-Enthalpy
Evaporator
Compressor
Condenser
Metering
Device
Pressure-Enthalpy (PH) diagram for refrigerant blends
Dew Point - Used to
determine superheat
Psia
Condenser
Compressor
Evaporator
Liquid psig
refrigerant bubble point
Metering
device
Liquid receiver
Vapor psig
refrigerant dew point
19
Superheat temperature measurement points.
For use with:
Fluke 116