Information
MDAReport
M&DDemoKit
Page9of16
DriveInput
Voltage&Current
Phase‐Ground Harmonics A(V)
VoltageHarmonics
THDwithinlimit
ForVFDsTHD<6%isrecommendedTHD
LimitaccordingEN50160is8%
Phase‐Ground Harmonics B (A)
CurrentHarmonics
THDisquitehighbutduetothe
relativelylowloadnoeffectsonother
equipmentonthegridisexpected
Ifloadrises,problemsinthegridoccur
orsensitiveloadsareconnecteda
%TDDanalysisisrecommended
DriveInput
VoltageUnbalance
DriveInput
CurrentUnbalance