Application Note

7 Fluke Corporation Checking ground electrode impedance for commercial, industrial and residental buildings.
This method requires a low-impedance path in
parallel with the electrode under test. The ground
electrode of most facilities is in parallel with numer-
ous utility ground electrodes. These electrodes can
be pole electrodes, pole butt plates or un-insulated
neutral conductors. The impedance of the utility
ground electrodes usually combines into a very
low impedance.
Let’s take an example. Say you have 40 pole
electrodes of roughly 20
Ω each, and these elec-
trodes are connected together by a low-impedance
ground wire from pole to pole. The equivalent
resistance of the 40 electrodes in parallel is:
Since half an ohm is small compared to the resis-
tance we expect for our electrode under test, we can
assume that most of the measured resistance is due
to the earth resistance of the electrode under test.
There are some potential pitfalls for this method:
If you measure in the wrong place in the system,
you might get a hard-wired loop
resistance,
for example on a ground ring or on a bonded
lightning protection system. If you were intend-
ing to read earth resistance, measuring the
conductive loop would give unexpectedly low
resistance readings.
You may get low readings due to the interaction
of two very close, bonded electrodes, like buried
conduit, water pipes, etc.
The quality of the measurement depends on
the availability of parallel paths. If a building
is solely supplied by a generator or transformer
that has only a single electrode, the assumption
of multiple paths won’t work and the measure-
ment will indicate the earth resistance of
both electrodes.
This method will not measure
earth resistance.
A problem with the utility grounding system
might interfere with readings.
1
40 x
1
/
20Ω
R
eq
=
=
1
/
2
Ω
In general, if you get readings below 1 ohm,
double-check to make sure you are not measuring
a hard-wired conductive loop instead of the
earth resistance.
Two-pole Method
The two-pole method uses an “auxiliary electrode
such as a water pipe. Figure 11 shows the connec-
tions. The tester measures the combined earth
resistance of
the electrode
under test, the
earth resistance
of the auxiliary
electrode, and
the resistance
of the measure-
ment leads.
The assump-
tion is that the
earth resistance
of the auxil-
iary electrode
is very low,
which would
probably be
true for metal
pipe with-
out plastic
segments or
insulated joints.
The effect of the measurement leads may be
removed by measuring with the leads shorted
together and subtracting this reading from the final
measurement.
Although it’s convenient, be very careful using
the two-pole method:
A water pipe may have PVC components, which
could greatly increase its earth resistance. In
this case the two-point method would give an
excessively high reading.
The auxiliary electrode may not be outside the
influence of the electrode under test. In this case
the reading might be lower than
reality.
Because of the unknowns
involved in this technique, it is
recommended only when the
grounding system and auxiliary
electrode are well known.
#
(
0
0
#
3
%
EXT
34!24
$)30,!9
#(!.'%
/&&
2
!
2
3%,%#4
POLE POLE
POLE
'ROUND
2ESISTANCEK
!#2ESISTANCE
K
3!452.'%/
./2-!%ARTH'ROUND4ESTER
3OURCE
-EASURE
#URRENT0ATHS
/&&
/.
/&&
/.
/&&
/.
/&&
/.
/&&
/.
/&&
/.
/&&
/.
/&&
/.
/&&
/.
Figure 10: Test current paths in the stakeless method
Electrode
Under test
#
(
0
0
#
3
%
EXT
34!24
$)30,!9
#(!.'%
/&&
2
!
2
3%,%#4
POLE POLE
POLE
'ROUND
2ESISTANCEK
!#2ESISTANCE
K
3!452.'%/
./2-!%ARTH'ROUND4ESTER
6
)
Figure 11: Equivalent circuit for two-point
measurement