Analyzer Instellen
MANUAL SETUP (Persoonlijke Instellingen)24
24-9
Tabel 24-1. Function Preference, Overzicht van Items voor Metingen
Metingen,
hoofditems
Metingen,
subitems
Fabrieksinstelling Metingen, subitem
instellingen
Trend Default duration 7 d 1 hr, 2 hr, 4 hr, 8 hr, 16 hr, 24 hr,
2 d, 7 d, 30 d,
3 mon, 6 mon, 12 mon.
Average time 1 s 0.25 s, 0.5 s, 1 s, 3 s, 5 s, 10 s,
30 s, 1 m, 5 m, 10 m, 15 m, 30 m
, 1 hr, 2 hr.
Start Delay 10 s 10 … 999 s (step: 1s)
Harmonics Scale % f % f, % r, rms
Interharmonics OFF ON, OFF
THD 40 harmonics 40, 50 harmonics
K-factor method
1
US EU, US
K-factor e
1
0.1 0.00 ... 0.20 (step 0.01)
K-factor q
1
1.7 1.00 ... 2.00 (step 0.01)
Dips & Swells Reference Nominal Nominal, sliding
Flicker Lamp model Fnom 50Hz/230V, 60Hz/120V
Phasor Clockwise neg neg, pos
Power Method Unified Classic, Unified
Display Fnom = 50Hz: Cos Φ
Fnom = 60Hz: DPF
Cos Φ, DPF
Cycle aggregation Interval 10/12 cycles
400 Hz: 80 cycles fixed
10/12 cycles,
150/160 cycles (3s)
1
Als de K-factor methode op US ingesteld wordt zijn de ‘K-factor e’ en de ‘K-factor q’ parameter uitgezet.
10
Wave Capture (functietoets F1): hier kunnen parameters ingesteld
worden die betrekking hebben op de acquisitie van spannings- en
stroomgolfvormen in functies zoals Transients en Flicker. In dit menu
kan functietoets F4 gebruikt worden om de fabrieksinstellingen te
kiezen, en F5 om het menu te verlaten.
11
Inrush (functietoets F2): menu om de default parameters voor
Inrushmetingen in te stellen. In dit menu kan F5 gebruikt worden om
het menu te verlaten..