Application Note
8 Fluke Corporation  Troubleshooting power harmonics
The presence of harmonics 
was obvious by comparison of 
phase current and neutral cur-
rent measurements. As Table 1 
shows, the neutral current was 
substantially higher than any of 
the phase currents, even though 
the phase currents were relatively 
well balanced. The average-
responding meter consistently 
took readings approximately 20 
percent low on all the phases. 
Its neutral current readings were 
only 2 percent low.
The waveforms explain the 
discrepancy. The phase currents 
were badly distorted by large 
amounts of third harmonic cur-
rent, while the neutral current 
was nearly a pure sinewave at 
the third harmonic frequency. 
The phase current readings 
listed in Table 1 demonstrate 
clearly why true-rms measure-
ment capability is required to 
accurately determine the value of 
harmonic currents.
The next step was to calculate 
the “harmonic derating factor” or 
HDF (Refer to “Derating trans-
formers” section on page 6.)
The results indicated that, 
with the level of harmonics 
present, the transformer should 
be derated to 72.3 percent of 
its nameplate rating to prevent 
overheating. In this case the 
transformer should be derated 
to 72.3 percent of its 225 kVA 
rating, or derated to 162.7 kVA.
The actual load was calcu-
lated to be 151.3 kVA. Although 
that figure was far less than the 
nameplate rating, the transformer 
was operating close to its derated 
capacity.
Subpanel—Next a subpanel 
which supplied branch circuits 
for the 120 V receptacles was 
examined. The current in each 
neutral was measured and 
recorded (see Table 2).
When a marginal or over-
loaded conductor was identified, 
the associated phase currents 
and the neutral-to-ground 
voltage at the receptacle were 
also measured. When a check 
of neutral #6 revealed 15 A in 
a conductor rated for 16 A, the 
phase currents of the circuits 
Figure 4. Phase current.
Figure 5. Neutral current.
Circuit 
number
Phase 
current 
(amps)
Neutral-to-ground voltage 
drop at receptacle
25 7.8 3.75 V
27 9.7 4.00 V
29 13.5 8.05 V
Table 3. Phase currents and neutral-to-ground voltage for neutral #06.
Neutral  
conductor 
number
Current 
(amps)
01  5.0
02 11.3
03  5.0
04 13.1
05 12.4
06 15.0*
07  1.8
08 11.7
09  4.5
10 11.8
11  9.6
12 11. 5
13 11.3
14  6.7
15  7.0
16  2.3
17  2.6
Table 2. Subpanel branch circuit neutral 
currents.
(#25, #27, and #29) that shared 
that neutral were also measured 
(Table 3). Note that each of the 
phase currents of these three 
branch circuits was substan-
tially less than 15 A, and also 
the same phase conductors had 
significant neutral-to-ground 
voltage drops.
In the branch circuits which 
had high neutral current, the 
relationship between the neutral 
and the phase currents was 
similar to that of the transformer 
secondary. The neutral cur-
rent was higher than any of the 
associated phase currents. The 
danger here is that the neutral 
conductors could become over-
loaded and not offer the warning 
signs of tripped circuit breakers.
Recommendations
1.  Refrain from adding addi-
tional loads to the receptacle 
transformer unless steps are 
taken to reduce the level of 
harmonics.
2.  Pull in extra neutrals to the 
branch circuits that are heav-
ily loaded.
3.  Monitor the load currents on a 
regular basis using true-rms 
measuring test equipment.
Fluke Corporation 
PO Box 9090, Everett, WA 98206 U.S.A.
Fluke Europe B.V. 
PO Box 1186, 5602 BD 
Eindhoven, The Netherlands
For more information call: 
In the U.S.A. (800) 443-5853 or  
Fax (425) 446-5116 
In Europe/M-East/Africa +31 (0) 40 2675 200 or  
Fax +31 (0) 40 2675 222 
In Canada (800)-36-FLUKE or  
Fax (905) 890-6866 
From other countries +1 (425) 446-5500 or  
Fax +1 (425) 446-5116 
Web access: http://www.fluke.com
©2003-2009 Fluke Corporation.  
Specifications subject to change without notice.  
Printed in U.S.A. 6/2009 1260362K A-EN-N
Modification of this document is not permitted 
without written permission from Fluke Corporation.
Fluke.  Keeping your world 
  up and running.
®








