Application Note
7 Fluke Corporation  Troubleshooting power harmonics
The high voltage and current 
present in electrical power 
systems can cause serious 
injury or death by electrocu-
tion. Consequently, only trained, 
experienced electricians who 
have knowledge of electri-
cal systems in general and the 
equipment under test should 
perform testing and modification 
of electrical systems.
Fluke cannot anticipate all 
possible precautions that you 
must take when performing the 
measurements described here. 
At a minimum, however, you 
should: 
•
  Use appropriate safety equip-
ment such as safety glasses, 
insulating gloves, insulating 
mats, etc.
•
  Be sure that all power has 
been turned off, locked out, 
and tagged in any situation 
where you will be in direct 
contact with circuit compo-
nents. Be certain that the 
power can’t be turned on by 
anyone but you.
•
  Read and understand all of 
the applicable manuals before 
using the application informa-
tion in this application note. 
Take special note of all safety 
precautions and warnings in 
the instruction manuals.
This article is a general guide to 
understanding harmonics. It is 
not intended to substitute for the 
services of a professional electri-
cal systems consultant. Before 
you take any measures to diag-
nose or address your potential 
harmonics problems, you should 
have your operation thoroughly 
analyzed by a professional elec-
trical engineer.
Situation
A modern office building dedi-
cated primarily to computer 
software development contained 
a large number of personal com-
puters and other electronic office 
equipment. These electronic 
loads were fed by a 120/208 V 
transformer configured with a 
delta primary and a wye second-
ary. The PCs were fairly well 
distributed throughout the build-
ing, except for one large room 
that contained several machines. 
The PCs in this room, used exclu-
sively for testing, were served by 
several branch circuits.
The transformer and main 
switch gear were located in a 
ground floor electrical room. 
Inspection of this room immedi-
ately revealed two symptoms of 
high harmonic currents:
•
  The transformer was generat-
ing a substantial amount of 
heat.
•
  The main panel emitted an 
audible buzzing sound. The 
sound was not the chatter 
commonly associated with 
a faulty circuit breaker, but 
rather a deep resonant buzz 
that indicated the mechanical 
parts of the panel itself were 
vibrating.
Ductwork installed directly over 
the transformer to carry off some 
of the excess heat kept the room 
temperature within reasonable 
limits.
Defining the problem
Transformer – Current mea-
surements (see Table 1) were 
taken on the neutral and on 
each phase of the transformer 
secondary using both a true-rms 
multimeter and an average-
responding unit. A 600 A 
clamp-on current transformer 
accessory was connected to each 
meter to allow them to make 
high current readings. The cur-
rent waveshapes are shown in 
Figures 4 and 5.
Conductor name
True-rms multimeter 
(amps)
Average responding 
multimeter (amps)
Instantaneous peak 
current (amps)
Phase 1 410 328 804
Phase 2 445 346 892
Phase 3 435 355 828
Neutral 548 537 762
Work safely
Case study








