Application Note
6 Fluke Corporation  Troubleshooting power harmonics
The following are suggestions 
of ways to address some typi-
cal harmonics problems. Before 
taking any such measures you 
should call a power quality 
expert to analyze the problem 
and design a plan tailored to 
your specific situation.
In overloaded neutrals
In a three-phase, four-wire 
system, the 60 Hz portion of the 
neutral current can be minimized 
by balancing the loads in each 
phase. The triplen harmonic 
neutral current can be reduced 
by adding harmonic filters at the 
load. If neither of these solutions 
is practical, you can pull in extra 
neutrals —ideally one neutral for 
each phase—or you can install 
an oversized neutral shared by 
three phase conductors.
In new construction, under 
carpet wiring and modular office 
partitions wiring should be 
specified with individual neutrals 
and possibly an isolated ground 
separate from the safety ground.
Derating transformers
One way to protect a trans-
former from harmonics is to limit 
the amount of load placed on 
it. This is called “derating” the 
transformer. The most rigorous 
derating method is described 
in ANSI/IEEE standard C57.110-
1986. It is somewhat impractical 
because it requires extensive 
loss data from the transformer 
manufacturer plus a complete 
harmonic spectrum of the load 
current.
The Computer & Business 
Equipment Manufacturers Associ-
ation has recommended a second 
method that involves several 
straightforward measurements 
that you can get with com-
monly available test equipment. 
It appears to give reasonable 
results for 208/120 V receptacle 
transformers that supply low 
frequency odd harmonics (third, 
fifth, seventh) commonly gener-
ated by computers and office 
machines operating from single-
phase branch circuits.
Derating factor
To determine the derating factor for the transformer, take the peak and true-
rms current measurements for the three phase conductors. If the phases are not 
balanced, average the three measurements and plug that value into the follow-
ing formula:
HDF  =  Harmonic derating factor
  =  (1.414)(true-rms phase current)
(Instantaneous peak phase current)
This formula generates a value between 0 and 1.0, typically between 0.5 
and 0.9. If the phase currents are purely sinusoidal (undistorted) the instanta-
neous peaks are 1.414 times the true-rms value and the derating factor is 1.0. 
If that is the case no derating is required.
However, with harmonics present the transformer rating is the product of the 
nameplate kVA rating times the HDF.
kVA derated = (HDF) x (kVA nameplate)
For example: 208/120 Y transformer rated at 225 kVA:
Conductor 
name
True-rms  
current amps
Instantaneous 
peak current
Load currents were measured with 
a Fluke Model 87 and an 80i-600 ac 
current probe to produce the follow-
ing results:
01 410  A 804 A
02 445 A 892 A
03 435 A 828 A
I phase avg.  =  410 + 445 + 435  =  430 A
   3
I pk avg.   =  804 + 892 + 828  =  841 A
   3
HDF  =  (1.414) (430)  =  72.3 %
    841
The results indicate that with the level of harmonics present the transformer
should be derated to 72.3 % of its rating to prevent overheating.
Solving the problem








