Application Note
4 Fluke Corporation  Troubleshooting power harmonics
Finding harmonics
Generators
Standby generators are subject 
to the same kind of overheat-
ing problems as transformers. 
Because they provide emergency 
backup for harmonic producing 
loads such as data processing 
equipment, they are often even 
more vulnerable. In addition to 
overheating, certain types of 
harmonics produce distortion at 
the zero crossing of the current 
waveform, which causes inter-
ference and instability for the 
generator’s control circuits.
Classification of harmonics
Each harmonic has a name, frequency and sequence. The sequence refers 
to phasor rotation with respect to the fundamental (F), i.e., in an induction 
motor, a positive sequence harmonic would generate a magnetic field that 
rotated in the same direction as the fundamental. A negative sequence har-
monic would rotate in the reverse direction. The first nine harmonics along 
with their effects are listed below:
Name F   2nd* 3rd   4th* 5th   6th* 7th   8th* 9th
Frequency 60 120 180 240 300 360 420 480 540
Sequence + — 0 + — 0 + — 0
*Even harmonics disappear when waves are symmetrical (typical for electrical circuits)
Sequence Rotation Effects (from skin effect, eddy currents, etc.)
Positive Forward Heating of conductors, circuit breakers, etc.
Negative Reverse Heating as above plus motor problems
Zero** None Heating, plus add in neutral of 3-phase, 4-wire system
**Zero sequence harmonics (odd multiples of the 3rd) are called “Triplens” (3rd, 9th, 15th, 21st, etc.)
A harmonic survey will give you 
a good idea if you have a prob-
lem and where it is located. Here 
are a few guidelines to follow.
1. Load inventory. Make a 
walking tour of the facility 
and take a look at the types of 
equipment in use. If you have 
a lot of personal computers 
and printers, adjustable speed 
motors, solid-state heater 
controls, and certain types of 
fluorescent lighting, there’s a 
good chance that harmonics 
are present.
2. Transformer heat check. 
Locate the transformers feed-
ing those non-linear loads and 
check for excessive heating. 
Also make sure the cooling 
vents are unobstructed.
3. Transformer secondary 
current. Use a three-phase 
true-rms power quality 
analyzer to check transformer 
currents.
•
 Verify that the voltage rat-
ings for the clamp meter are 
adequate for the transformer 
being tested.
•
 Measure and record the 
transformer secondary cur-
rents in each phase and in 
the neutral (if used).
•
 Compare the kVA deliv-
ered to the load against the 
nameplate rating. (If har-
monic currents are present, 
the transformer can overheat 
even if the kVA delivered 
is less than the nameplate 
rating.)
•
 Use the k-factor measure-
ment from a three-phase 
analyzer to determine 
de-rating or transformer 
replacement.
•
 Measure the frequency of 
the neutral current. 180 Hz 
would be a typical reading 
for a neutral current consist-
ing of mostly third harmonic.
4. Sub-Panel neutral current 
check. Survey the sub-
panels that feed harmonic 
loads. Measure the current 
in each branch neutral and 
compare the measured value 
to the rated capacity for the 
wire size used. Check the 
neutral bus bar and feeder 
connections for heating or 
discoloration. A non-contact 
infrared thermometer, like the 
Fluke 61, is useful for detect-
ing excessive overheating on 
bus bars and connections.
5. Receptacle neutral-to-
ground voltage check. 
Neutral overloading in 
receptacle branch circuits 
can sometimes be detected 
by measuring the neutral-
to-ground voltage at the 
receptacle.
•
 Measure the voltage when 
the loads are on. Two volts 
or less is about normal. 
Higher voltages can indicate 
trouble depending on the 
length of the run, quality of 
connections, etc. Measure 
the frequency. A frequency 
of 180 Hz would suggest 
a strong presence of har-
monics, while 60 Hz would 
suggest that the phases are 
out of balance. Pay special 
attention to under carpet 
wiring and mod-ular office 
panels with integrated 
wiring that uses a neutral 
shared by three-phase 
conductors.
•
 Because the typical loads in 
these two areas are com-
puter and office machines, 
they are often trouble spots 
for overloaded neutrals.








