Application Note
3 Fluke Corporation  Troubleshooting power harmonics
Symptoms of harmonics usually 
show up in the power distribu-
tion equipment that supports the 
non-linear loads. There are two 
basic types of non-linear loads: 
single-phase and three-phase. 
Single-phase, non-linear loads 
are prevalent in offices, while 
three-phase loads are wide-
spread in industrial plants. 
Each component of the power 
distribution system manifests 
the effects of harmonics a little 
differently, yet all are subject to 
damage and inefficient perfor-
mance if not designed to handle 
electronic loads.
Neutral conductors
In a three-phase, four-wire 
system, neutral conductors can 
be severely affected by non-
linear loads connected to the 120 
V branch circuits. Under normal 
conditions for a balanced linear 
load, the fundamental 60 Hz 
portion of the phase currents will 
cancel in the neutral conductor.
In a four-wire system with 
single-phase, non-linear loads, 
certain odd-numbered harmon-
ics called triplens—odd multiples 
of the third harmonic: 3rd, 9th, 
15th, etc—do not cancel, but 
rather add together in the neutral 
conductor. In systems with many 
single-phase, non-linear loads, 
the neutral current can actually 
exceed the phase current. The 
danger here is excessive over-
heating because, unlike phase 
conductors, there are no circuit 
breakers in the neutral conductor 
to limit the current.
Excessive current in the neu-
tral conductor can also cause 
higher-than-normal voltage 
drops between the neutral con-
ductor and ground at the 120 V 
outlet.
Circuit breakers
Common thermal-magnetic 
circuit breakers use a bi-metallic 
trip mechanism that responds to 
the heating effect of the circuit 
current. They are designed to 
respond to the true-rms value of 
the current waveform and will 
trip when the trip mechanism 
gets too hot. This type of breaker 
has a good chance of protect-
ing against harmonic current 
overloads.
A peak-sensing, electronic trip 
circuit breaker responds to the 
peak of current waveform. As a 
result, it won’t always respond 
properly to harmonic currents. 
Since the peak of the harmonic 
current is usually higher than 
normal, this type of circuit 
breaker may trip prematurely at a 
low current. If the peak is lower 
than normal, the breaker may 
fail to trip when it should.
Bus bars and  
connecting lugs
Neutral bus bars and connecting 
lugs are sized to carry the full 
value of the rated phase current. 
They can become overloaded 
when the neutral conductors are 
overloaded with the additional 
sum of the triplen harmonics.
Electrical panels
Panels that are designed to carry 
60 Hz currents can become 
mechanically resonant to the 
magnetic fields generated by 
higher frequency harmonic 
currents. When this happens, 
the panel vibrates and emits a 
buzzing sound at the harmonic 
frequencies.
Telecommunications
Telecommunications systems 
often give you the first clue to 
a harmonics problem because 
the cable can be run right next 
to power cables. To minimize 
the inductive interference from 
phase currents, telecommunica-
tions cables are run closer to the 
neutral wire.
Triplens in the neutral conduc-
tor commonly cause inductive 
interference, which can be heard 
on a phone line. This is often the 
first indication of a harmonics 
problem and gives you a head 
start in detecting the problem 
before it causes major damage.
Transformer
Commercial buildings commonly 
have a 208/120 V transformer 
in a delta-wye configuration. 
These transformers commonly 
feed receptacles in a commer-
cial building. Single-phase, 
non-linear loads connected to 
the receptacles produce triplen 
harmonics, which add up in the 
neutral. When this neutral cur-
rent reaches the transformer, it is 
reflected into the delta primary 
winding where it causes over-
heating and transformer failures.
Another transformer problem 
results from core loss and copper 
loss. Transformers are normally 
rated for a 60 Hz phase current 
load only. Higher frequency har-
monic currents cause increased 
core loss due to eddy currents 
and hysteresis, resulting in more 
heating than would occur at the 
same 60 Hz current.
These heating effects demand 
that transformers be derated for 
harmonic loads or replaced with 
specially designed transformers.
Effects of harmonic currents
01 
02 
03
120 V Branch Circuits
208/480 Volt Transformer
Secondary
Primary
Neutral
A
B
C








