User's Manual
Setting up a Measurement
Auto-Trigger 5
5-27
When Auto-Trigger is selected all Recording Modes settings are pre-configured with
the fixed values below.
Table 5-1. Pre-configured Recording Modes
Virtual
Instrument
Aggregation Pre-Trigger Recording time Holdoff time
RMS 10/20 ms
1
sliding
0.5 sec 5 sec 10 sec
Harmonics 200 ms 2 sec 15 sec 10 sec
Oscilloscope Sample 0.1 sec 0.2 sec 3 sec
Transients 500 kHz 11.08 msec 32.768 msec 5 sec
1
RMS recording uses half cycle values or full cycle values updated every half cycle, whatever
is configured in the Nominal / Limit values settings dialog.
In Trigger Settings only Ripple Control Trigger and Time Trigger can be edited:
triggersettingsat.bmp