User's Manual

PC Software for 1740 Series
PQ Log Feature Reference
49
Note
An exceeding occurs when the mean measured value Plt (according to the
EN 50160 standards, the mean value Plt is calculated over twelve
10 minute mean values Pst) is above or below the limit value. The standard
is met if 95 % of all measured values are below the limit value.
Voltage Unbalance
This option indicates the limit value for permissible voltage unbalance in three phase
systems.
Note
An exceeding occurs if the measured mean value (according to the EN-
50160 standard, the 10 minute mean value) is above the limit value. The
standard is met if 95 % of all measured values are below the limit value.
Number of Allowed Events
Determines the permissible number of events. The standard does not prescribe a value.
The default value is 100 events during one week.
Interruption Limit
Allows you to define the threshold for interruptions in % of V
n
. A dip below this value
will be considered an interruption.
Interharmonics
Opens the Limit value level file - Interharmonics screen. It indicates the limit values for
interharmonics.
Voltage Harmonics
Opens the Limit value level file - Voltage Harmonics screen. It indicates the limit values
for harmonics and the thd.
Current Harmonics
This function is similar to voltage harmonics. This button opens the “Limit value level
file – Current Harmonics” screen. Limit values for individual current harmonics and the
thd can be defined in this screen.
Tip for Central European Distribution Networks
A very important task for utilities is to assess the additional network distortion produced
by new consumers which are to be connected to the network.
There are clearly defined emission levels for each single current harmonic to further
ensure safe and correct operation of all consumers in the network without any failures.
There is a recommendation issued by experts of the Austrian E-CONTROL, the Austrian
VEÖ, the Swiss VSE, the German VDN and the Czech CSRES, which prescribes a
procedure for assessing the impact of new appliances to the distribution network which
can be carried out easily with the Logger product range with the measuring function A.
The Procedure in General:
For a specific installation there are some parameters which provide us with the relevant
basic information: