Data Sheet
3 Fluke Corporation 1735 Three-Phase Power Logger
Specifications
General
Display ¼ VGA Graphic Color transmissive displays 320 x 240 Pixel with additional background lighting and adjustable
contrast, text and graphics in color
Quality Developed, designed and manufactured according to DIN ISO 9001
Memory 4 MB Flash memory, 3.5 MB for logging data
Interface RS-232 SUB-D socket; 115.2 k Baud, 8 data bits, no parity, 1 stop bit, firmware updates are possible with the
RS-232 interface (9-pole extension cable)
Sample rate 10.24 kHz
Line frequency 50 Hz or 60 Hz, user-selectable, with automatic synchronization
Power supply NiMH battery-pack, with ac adapter (15 V to 20 V/0.8 A)
Operation time with battery Typical > 12 hours with backlight low and > 6 hours with backlight high
Dimensions 240 mm x 180 mm x 110 mm (6.1 in x 4.6 in x 2.8 in)
Weight 1.7 kg (3.75 lb), including battery
Ambient conditions
Working temperature range -10 °C to +50 °C (+14 °F to +122 °F)
Storage temperature range -20 °C to +60 °C (+32 °F to +140 °F)
Operating temperature range 0 °C to +40 °C (+32 °F to +104 °F)
Reference temperature range 23 °C ± 2 °C
Note: The above terms are defined in European Standards. To calculate the specification at any point in the working temperature range, use the temperature
coefficient below.
Temperature coefficient ± 0.1 % of the measured value per °C from the reference
Intrinsic error Refers to reference temperature, max. deviation is guaranteed for two years.
Operating error Refers to operating temperature range, max. deviation is guaranteed for two years
Climatic class C1 (IEC 654-1) -5 °C to +45 °C (+41 °F to +113 °F), 5 % to 95 % RH, no dew
Housing Cycoloy shock and scratch proof thermoplast V0-type (non-flammable) with rubber protection holster
EMC
Emission IEC/EN 61326-1:1997 class B
Immunity IEC/EN 61326-1:1997
Safety
Safety IEC 61010-1 600 V CAT III, double or reinforced insulation, pollution degree 2
Protection IP65; EN60529 (refers only to the main housing without the battery compartment)
RMS values are measured with a 20 ms resolution.
V-rms wye measurement
Measuring range 57 V/66 V/110 V/120 V/127 V/220 V/
230 V/240 V/260 V/277 V/347 V/
380 V/400 V/417 V/480 V ac
Intrinsic error ± (0.2 % of measured value. + 5 digits)
Operating error ± (0.5 % of m. v. + 10 digit)
Resolution 0.1 V
V-rms delta measurement
Measuring range 100 V/115 V/190 V/208 V/220 V/380 V/
400 V/415 V/450 V/480 V/600 V/
660 V/690 V/720 V/830 V ac
Intrinsic error ± (0.2 % of m. v. + 5 digit)
Operating error ± (0.5 % of m. v. + 10 digit)
Resolution 0.1 V