Operation Manual
LinkWare Cable Test Management Software
Getting Started Guide
22
alp03.eps
Figure 6. Fiber Cable Report from OptiFiber Tester, Page 2
Cable ID: FIBER 8 Test Summary: FAIL
Date / Time: 06/24/2004 09:07:44am
Headroom: -2.06 dB (Loss)
Cable Type: 3M Volition, 50
End1: DATA CENTER
End2: CLOSET
Model: OptiFiber
Project: OptiFiber Record Examples Telecom Room: 2B
Site: Fluke Networks Rack: B
Building: Fluke Park Patch: D
Floor: 2 FNet.flw
ChannelMap
Date / Time: 06/24/2004 07:59:40am
Tester: OptiFiber (9999923 V1.7.221)
Module: OFTM-5612 (9999918 V1.7.221)
Operator: PETER STUART
Fiber Length: 1102 m
End1 End2
DATA CENTER CLOSET
104 m 997 m 1 m
Loss/Length End2-1 FAIL
Date / Time: 06/24/2004 07:55:37am
Test Limit: ISO 11801:2002 Chan
Cable Type: 3M Volition, 50
Number of Adapters: N/A
Number of Splices: N/A
Tester: OptiFiber (9999923 V1.7.221)
Module: OFTM-5612 (9999918 V1.7.221)
Operator: PETER STUART
Patch Length1 (m): 2.0
Patch Length2 (m): 2.0
Patch Length3 (m): 0.3
Loss Loss Length
Prop.
Delay
Result
Value
Limit
Margin
Reference
(Method B)
850 nm
FAIL
5.97 dB
4.00 dB
-1.97 dB
-19.10 dBm
1300 nm
FAIL
4.25 dB
4.00 dB
-0.25 dB
-20.14 dBm
n=1.4860
PASS
997.6 m
2000.0 m
1002.4 m
N/A
4944.4 ns
Reference Date: 06/23/2004 10:27:03am
Loss/Length End1-2 FAIL
Date / Time: 06/24/2004 07:55:03am
Test Limit: ISO 11801:2002 Chan
Cable Type: 3M Volition, 50
Number of Adapters: N/A
Number of Splices: N/A
Tester: DTX-1800R (HM03R v1.0004)
Module: DTX-MFM (8582005 v1.0004)
Operator: PETER STUART
Patch Length3 (m): 0.3
Loss Loss Length
Prop.
Delay
Result
Value
Limit
Margin
Reference
(Method B)
850 nm
FAIL
6.06 dB
4.00 dB
-2.06 dB
-16.34 dBm
1300 nm
FAIL
5.23 dB
4.00 dB
-1.23 dB
-18.44 dBm
n=1.4860
PASS
997.6 m
2000.0 m
1002.4 m
N/A
4944.4 ns
Reference Date: 06/23/2004 10:27:03am