Instructions

12
SimpliFiber Pro Getting Started Guide
To set the reference:
1
Clean the connectors on the meter, source, and a test
reference cord. Use fiber optic solvent and optical-grade
wipes or swabs to clean connectors as described in the
Users Manual.
2
Turn on the meter and source and let them warm up for 5
minutes. Allow additional time if the equipment has been
stored above or below ambient temperature.
3
Make the connections shown below.
4
If the source’s AUTO LED is not on, press .
If you want to set the reference for both wavelengths, press
until the wavelength LEDs blink alternately.
5
On the meter, press until POWER appears.
6
Press SET REF. The meter switches to loss mode, the
display shows
 dB, OK appears briefly, and the new
reference value appears.
Caution
If you disconnect the source’s output after setting the
reference, you must set the reference again to ensure
valid measurements.
ffl07.eps
Reference Connections
Test reference cord
Meter Source
Caution
Do not disconnect the test
reference cord from the source’s
output after setting the
reference.