Operation Manual

How to Test Your Test Reference Cords
1. Set Up the Tester
A-3
A
1. Set Up the Tester
1-1
Turn on the tester. Wait for a minimum of 5 minutes for
the tester to become stable. Wait for a longer time if the
tester is much colder or hotter than the work area.
1-2
Turn the rotary switch to SETUP, then make these
settings:
Test Limit: Select the applicable limit:
Fiber Type: Select the type of cable you will test.
This sets the index of refraction (n). The test limits
shown above use n to calculate the length of the
fiber, then they use the length to calculate the limit
for loss. Thus, you must use the correct value of n to
get an accurate measurement of loss. If you cannot
find the correct fiber type, you can enter the value
of n for your fiber on tab 3 of the setup menus. Get
the value of n from the cable vendor.
Remote End Setup: Loopback
Bi-Directional: Yes
Number of Adapters: 2 (see note below)
Connector Type: Select the type of connector that is
on the cords you will test
Test Method: 1 Jumper
Note
Though this procedure uses 1 adapter, use “2” for
the Number of Adapters setting. Ignore the test
limit that the tester uses, and compare the loss
measurements to the values given in step 5.
Standard
Test Limit for
Multimode
Test Limit for
Singlemode
ANSI/TIA-568-C TIA-568-C
Multimode
TIA-568-C
Singlemode ISP
ISO/IEC 14763-3 ISO/IEC 14763-3 ISO/IEC 14763-3