30
Certifying Coaxial Cabling
Certifying coaxial cabling requires the optional
DTX-COAX coaxial adapters.
Setting the Reference for Coaxial Cabling
The reference procedure sets a baseline for insertion loss
measurements.
Run the tester’s reference procedure at the following
times:
When you want to use the tester with a different
smart remote. You can reference the tester to two
different smart remotes.
Every 30 days. Doing so ensures maximum accuracy of
test results.
You do not need to set the reference after changing link
interface adapters.
Note
Turn on the tester and let it sit for 1 minute before
setting the reference. Set the reference only after
the testers have reached an ambient temperature
between 10
C and 40
C (50
F and 104
F).