Certifying Twisted Pair Cabling
Setting the Reference for Twisted Pair Cabling
The reference procedure sets a baseline for insertion loss,
ACR-F, and DC resistance measurements.
Run the tester’s reference procedure at the following
times:
When you want to use the tester with a different
smart remote. You can reference the tester to two
different smart remotes.
Every 30 days. Doing so ensures maximum accuracy of
test results.
You do not need to set the reference after changing link
interface adapters.
Note
Turn on the tester and smart remote and let them
sit for 1 minute before setting the reference. Set
the reference only after the testers have reached
an ambient temperature between 10
C and 40
C
(50
F and 104
F).
To set the reference, do the following:
1
Use one of the methods shown in Figure 9 to connect
the main and remote testers together..
Caution
When you use two channel adapters for the
reference procedure, use only the 6 inch (15 cm)
patch cord provided with the DTX-1500 to
connect the testers together.
2
Turn the rotary switch to SPECIAL FUNCTIONS.
3
Highlight Set Reference; then press .
4
Press .