User Manual
Qualifying Cabling with the Autotest
19
Autotest on Twisted Pair Cabling
Notes
A wiremap adapter or remote ID locator must be
connected to the end of the cabling for the
wiremap to be completely verified.
The Autotest does not support use of multiple
remote ID locators (the MultiMap function).
If you use patch cords at the near or far end
during an Autotest, Fluke Networks recommends
patch cords at least 2 m long.
The Autotest will not run if the tester is
connected to a data port, or detects voltage or a
short on the cabling.
1 Turn on the tester. Turn the rotary switch to
AUTOTEST.
2 To change the tests to run,
J or H. See page 18.
3 Connect the tester and wiremap adapter or ID locator
to the cabling. Figures 6, 7, and 8 show typical
connections.
4 Press
P. The Autotest proceeds when a wiremap
adapter or ID locator is detected. The analog toner
turns on if neither is detected.
5 To save the test:
a. Press
K S.
b. Use
AD and H to select the Site, Location,
or Outlet field for editing. You can enter up to
17 characters in each field. See Figure 4 on page
13 for details on editing text.
To see a list of predefined labels for the
highlighted field, press J List. Use AD,
B C, or SHIFT + AD to move through the
list. Use
H or J to select an entry.
c. On the Enter ID screen, press
K S to save
the results with the Site, Location, and Outlet
entries shown.
Note
The last character of the Outlet string increments
each time you save an Autotest.