User Manual
Table Of Contents
- CableIQ™ Qualification Tester Users Manual
- LIMITED WARRANTY AND LIMITATION OF LIABILITY
- Table of Contents
- List of Figures
- List of Tables
- Overview of Features
- Registration
- Contacting Fluke Networks
- Additional Resources for Cable Testing Information
- Unpacking
- Symbols and Safety Information
- Physical Features
- Using the Wiremap Adapter and Remote ID Locators
- Powering the Tester
- Verifying Operation
- Setting User Preferences
- Checking the Hardware and Software Versions
- Qualifying Cabling with the Autotest
- Discovering Cabling Characteristics
- Using the Toner
- Using the IntelliTone Cable Map Function
- Blinking a Port Light
- Testing for Continuity
- Using the Continuity Toner
- Locating Crosstalk and Impedance Faults on Twisted Pair Cabling
- Testing Speaker Cabling
- Calibrating Length Measurements
- Memory Functions
- Maintenance
- If Something Seems Wrong
- Options and Accessories
- Specifications
- Appendix A: Diagnosing Cabling Faults
- Index
CalibratingLengthMeasurements
61
DeterminingaCable’sActualNVP
Youcandetermineacable’sactualNVPbyadjustingthe
measuredlengthtomatchaknownlengthofcable.
Todetermineacable’sNVP:
1 Connectaknownlengthofthecabletobetestedto
thetester’stwistedpairorcoaxialconnector.The
cablelengthmustbeasfollows(asmeasuredusing
thetester’sdefaultNVPvalues):
• Twistedpair, Cat 6A and below:34.4ftto
689.7ft(10.5mto 210.2m)
• Coaxial:40.3ftto807.9ft(12.3mto246.2m)
Tip:Formaximumaccuracyandadjustmentresolution,
useacablebetween45ftand70ft(14mand
21m)long.
Note
Thecablemustnotbeconnectedtoawiremap
adapter,port,orotherdevice.
2 TurntherotaryswitchtoSETUP.
3 Use
DtohighlightLengthCalibration;thenpress
HorJ.
4 TosettheNVPforcoaxialcable,pressK
c.
5 PressHorJ;thenuseDAtochangethe
NVPuntilthemeasuredlengthmatchestheactual
lengthofthecable.
6 Press
HtosavetheNVPvalue.