Set the Reference
The reference procedure for twisted pair cable sets the baseline
for insertion loss, ACR-F, and DC resistance measurements.
Set the reference at these times:
When you want to use the tester with a different remote. You
can set the reference for eight different remotes.
When you attach Class F/F
A
link interface adapters, such as the
optional DSX-PLA011 TERA
adapters.
Every 30 days. This ensures maximum accuracy of test results.
To set the reference
1 Turn on the tester and the remote a minimum of 1 minute
before you set the reference.
Note
Set the reference only after the testers are at an
ambient temperature between 50 °F and 104 °F
(10 °C and 40 °C).
2 Connect the main and remote testers together as shown in
Figure 25.
3 If you attached Class F/F
A
link interface adapters, make sure
you select a Class F or F
A
test limit. See the documentation
supplied with the adapters.
4 On the home screen, tap TOOLS, then tap Set Reference.
5 On the SET REFERENCE screen tap TEST.