User's Manual

1750
Operators Manual
50
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
The term “IC:” before the radio certification number only signifies that Industry of
Canada technical specifications were met.
Specifications for the System: Recorder and Power Analyze
Software
General Specifications
Power Quality Measurement Standards
Conformance....................................................IEC 61999-1-4 Class 1, IEC 61000-4-30 Class A or B depending on
measurement function, IEEE519, IEEE1159, IEEE1459
Clock/Calendar.................................................Leap years, 24-hour clock
Real-time Clock Accuracy ...............................Not more than ± 0.3 s/day
Internal Memory Capacity for Data .................At least 1 GB
Maximum Recording Period............................At least 1 month
Measurement Time Control .............................Automatic
Maximum Number of Events ...........................Limited only by the size of the internal memory.
Power Requirements .......................................90 to 264 V rms ±10%, 47-63 Hz, 40 W
Operating Time During Interruptions
(internal UPS operation).....................................5 minutes per interruption, 60 minutes total operating time without
recharging
Dimensions ......................................................215 x 310 x 35 mm (8.5 x 12.2 x 3.5 inch)
Mass (Weight)...................................................6.3 kg (14 lbs)
Input Specifications
Measurement Types.........................................One Phase Plus Neutral, One Phase IT No Neutral, One Phase Split
Phase, Three Phase Wye, Three Phase Delta, Three Phase IT, Three
Phase High Leg, Three Phase Open Leg, 2 Element Delta, 2 ½
Element Wye
Input Channels.................................................Voltage: 5 channels, AC/DC
Current: 5 channels
Voltage Channels.............................................Input resistance: 2 M
Input capacitance: < 20 pF
Current Channels.............................................1 MΩ. Self-identifying probes
Types available: current clamps, Flexi-CTs
Measuring Method ...........................................Simultaneous digital sampling of voltage and current. Digital PLL
synchronized sampling, internal frequency reference used during
voltage drops.
Synchronization and Sampling
PLL-Synchronization Source ..........................The PLL synchronizes to the A-N voltage for wye power types, and t
the A-B voltage for delta power types. All listed power types can be
characterized as either wye or delta.
PLL Lock Range...............................................42.5 to 69 Hz
Sampling Frequency........................................Voltage and current: 256 samples/cycle
Inter-harmonics per IEC61000-4-7: 2560 points / 10 cycles (50 Hz),
3072 points/12 cycles (60 Hz)
Transient Voltage: 5 MHz
A/D Resolution .................................................Voltage and current: 24 bits
Transient voltage: 14 bits