Meter Screen
The Meter screen shows numeric readings for all selected phases.
Phasor Screen
The PHASOR screen shows voltage (long arrows with solid arrowheads), current
amplitudes, and phase angles. This screen is used to verify proper test lead and current
probe connections.
You can easily correct an erroneous Recorder connection by going directly to
Setup\Phase Swap (
) and using the Recorder to internally invert a CT, swap a voltage
or CT phase, or modify a scaling parameter, then return to the screen to verify that the
correction has been made. There is no need to touch the cables. See “Phase Swap” later in
the manual for additional information.